INSTALLATION INSTRUCTIONS
RECOMMENDED MODELS
P/N 006355
Notice to installing contractor:  Instructions must remain with installation.
FM0447
Rev. A
0823
Supersedes
0220
PREINSTALLATION CHECKLIST - ALL INSTALLATIONS
DATE INSTALLED:
MODEL NUMBER:
EFFLUENT*/SUMP/DEWATERING SEWAGE
55 / 59, 139 Series
140 / 4140, 145 / 4145, 160 / 4160 Series 270 / 4270 Series
180 / 4180, 191, 371, 372, 373 Series 280 / 4280, 290 / 4290 Series
Product information presented here reflects conditions at time of  publication. Consult factory regarding discrepancies or inconsistencies.
MAIL TO:  P.O. BOX 16347 • Louisville, KY  40256-0347
SHIP TO:  3649 Cane Run Road  • Louisville, KY  40211-1961
Tel: (502) 778-2731 • 1 (800) 928-PUMP 
Visit our website:
zoellerpumps.com
Trusted. Tested. Tough.
®
* Efuent systems should specify that pumps should not handle solids exceeding 3/4” (19 mm) in order to prevent large solids from entering leeching elds, mound 
systems, etc.  (70 Series have 3/8” (9 mm) solids capability.  50, 140/4140, 371 and 372 Series have 1/2” (13 mm), 130 Series has 5/8" (16 mm), 145/4145, 160/4160, 180/4180 
and 373 models have 3/4” [19 mm].)  Where code permits, sewage pumps can be used for efuent systems.  Non-automatic pumps with external-level controls are 
recommended for septic tank efuent applications.
1.    Inspect all materials. Occasionally, products are damaged during shipment. If the unit is damaged, contact  your dealer before using.  DO NOT remove the test plugs 
from the pump.
2.  Carefully read the literature provided to familiarize yourself with specic details regarding installation and use. These materials should be retained for future 
reference. 
SEE BELOW FOR 
LIST OF WARNINGS
CAUTION
SEE BELOW FOR 
LIST OF CAUTIONS
REFER TO WARRANTY ON PAGE 2.
  1.  To reduce the risk of electrical shock, a properly grounded receptacle or 
control box must be installed in accordance with the governing codes.  Never 
remove ground pin from plug. 
  2.  Make certain that the ground fault interrupter protected receptacle or control 
box is within the reach  of the pump’s power supply cord.  DO NOT USE AN 
EXTENSION CORD. Extension cords that are too long or too light do not deliver 
sufcient voltage to the pump motor, and they could present a safety hazard 
if the insulation were to become damaged or the connection end were to fall 
into a damp or wet area.
  3.  Make sure the pump's electrical supply circuit is equipped with fuses or circuit 
breakers of proper capacity.  A separate branch circuit is recommended, sized 
according to the local  electrical codes for the current shown on the pump 
name plate.
  4.  Testing for ground.  As a safety measure, each electrical outlet should be checked 
for ground using a circuit analyzer which will indicate if the power, neutral and 
ground wires are correctly connected to your outlet.  If they are not, call a quali-
ed licensed electrician.
  5.  FOR YOUR PROTECTION, ALWAYS DISCONNECT PUMP FROM ITS POWER 
SOURCE BEFORE HANDLING.  If pump is wired direct, de-energize the circuit 
at the control box. Wear insulated protective shoes and do not stand in water.  
Pumps equipped with a 3-prong ground plug are designed to help protect 
against electrical shock.  DO NOT, UNDER ANY CIRCUMSTANCES, REMOVE 
THE GROUND PIN.    
  6.  Installation and servicing of the pump, electrical circuits and hardware should 
only be performed by a qualied, licensed electrician.
  7.  Risk of electrical shock. Do not remove power supply cord and strain relief 
or connect conduit directly to the pump.  If the supply cable is damaged, it 
must be replaced by the Manufacturer or an Authorized Service and Warranty 
Center to avoid a hazard.
  8.  Pump contains oil which becomes pressurized and hot when operating.  Allow 
2-1/2 hours after disconnecting before attempting service.
  9.  Pump is not intended for potable water due to possible contamination by oil 
contained in the pump.
 10.  Risk of electrical shock. These pumps have not been investigated for use in 
swimming pools and marine areas.
 11. Prop65 Warning for California residents: Cancer and Reproductive Harm- 
www.P65Warnings.ca.gov.
  1.  Check to be sure your power source is capable of handling the voltage 
requirements of the motor, as indicated on the pump name plate.
  2.  The installation of variable level oat switches is the responsibility of the 
installing party, and care should be taken that the tethered oat  switch will 
not hang up on the pump apparatus or pit peculiarities and is secured so that 
the pump will shut off.  It is recommended to use rigid pipe and ttings and 
the pit be 18" (46 cm) or larger in diameter.
  3.  Vent hole.  It is necessary that all submersible sump, efuent, and sewage 
pumps capable of handling various sizes of solid waste be of the bottom intake 
design to reduce clogging and seal failures.  If a check valve is incorporated 
in the installation, a 3/16" (5 mm)vent hole must be drilled in the discharge pipe 
below the check valve and pit cover to purge the unit of trapped air.   Vent 
hole should be checked periodically for clogging.    The vent hole on a High 
Head application may cause too much turbulence. If you choose not to drill a 
vent hole, be sure the pump case and impeller is covered with liquid before 
connecting the pipe to the check valve. NOTE: THE HOLE MUST BE BELOW 
THE BASIN COVER AND CLEANED PERIODICALLY. Water stream will be visible 
when pump is operating.
  4.  Pump should be checked frequently for debris and/or build up which may 
interfere with the oat “on” or “off” position. Repair and service should be 
performed by an Authorized Service and Warranty Center.
  5.  Maximum operating temperature for standard model pumps must not exceed  
130 °F (54 °C). Maximum operating temperatures for 70 series and model 
211 must not exceed 110 °F (43 °C). Maximum operating temperatures 
for 73, 75, must not exceed 104 °F (40 °C). 
  6.  Do not operate a pump in an application where the Total Dynamic Head is 
less than the minimum Total Dynamic Head listed on the Pump Performance 
Curves.
   7.   For health reasons, do not unplug, turn off, or disable pump and use pump tank   
system as a way to ll up a sink or laundry tray, etc. 
8.   Pumps must be installed in accordance with the National Electrical Code and 
all applicable local codes and ordinances.  Pumps are not to be installed in 
locations classied as hazardous in accordance with National Electric Code, 
ANSI, NFPA 70.
NOTE: Pumps with the "UL" mark and pumps with the "US" mark are tested to UL 
standard UL778.  CSA certied pumps are certied to CSA standard C22.2 No. 108.
Register your 
Zoeller Pump Company 
Product on our website:
http://reg.zoellerpumps.com/
NOTICE: VENT HOLE FOR
CHECK VALVE
SEE #3 IN CAUTION SECTION
BELOW AND #4 ON PAGE 3
Many Zoeller products contain 
registered trademarks for 
design and/or the color green: 
U.S. #4,849,524 / #5,024,907
55, 57 pumps powered by  
Zoeller Motor Works motor
Tuotetiedot
| Merkki: | Zoeller | 
| Kategoria: | Loisto | 
| Malli: | M282 | 
Tarvitsetko apua?
Jos tarvitset apua merkille Zoeller M282 esitä kysymys alla ja muut käyttäjät vastaavat sinulle
Loisto Zoeller Käyttöohjeet
                        
                         27 Maaliskuuta 2025
                        
                    
                                                            
                        
                         27 Maaliskuuta 2025
                        
                    
                                                            Loisto Käyttöohjeet
- Loisto Topeak
- Loisto Worx
- Loisto Anova
- Loisto FIAP
- Loisto Ryobi
- Loisto Bestway
- Loisto Einhell
- Loisto Lezyne
- Loisto Little Giant
- Loisto Sauermann
- Loisto SKS
- Loisto Grundfos
- Loisto Interphone
- Loisto MSW
- Loisto Franklin Electric
Viimeisimmät Loisto Käyttöohjeet
                        
                         5 Huhtikuuta 2025
                        
                    
                                                            
                        
                         1 Huhtikuuta 2025
                        
                    
                                                            
                        
                         1 Huhtikuuta 2025
                        
                    
                                                            
                        
                         1 Huhtikuuta 2025
                        
                    
                                                            
                        
                         1 Huhtikuuta 2025
                        
                    
                                                            
                        
                         1 Huhtikuuta 2025
                        
                    
                                                            
                        
                         1 Huhtikuuta 2025
                        
                    
                                                            
                        
                         1 Huhtikuuta 2025
                        
                    
                                                            
                        
                         1 Huhtikuuta 2025
                        
                    
                                                            
                        
                         1 Huhtikuuta 2025