DRAIN PUMP SYSTEMS 
MODELS 104*, 105, 110, 115, 120, 131
 INSTALLATION INSTRUCTIONS 
PREINSTALLATION CHECKLIST
P/N 017583
SECTION: 6.10.045
FM2336
1113
Supersedes
0612
Notice to Installer:  Instructions must remain with installation.
MODEL: ______________________
DATE CODE:  __________________
DATE INSTALLED:   _____________
1.    Inspect your unit. Occasionally, products are damaged during shipment. If the unit is damaged, contact  your dealer before using.    remove the test DO NOT
plugs from the pump. 
2.    Carefully read the literature provided to familiarize yourself with specic details regarding installation and use. These materials should be retained for future reference. 
1.  To reduce the risk of electrical shock, a properly grounded receptacle of grounding 
type must be installed and protected by a ground fault circuit interrupter (GFCI) 
and in accordance with National Electrical Code and local codes. 
  (SEE WARNING BELOW) 
2.  Make certain that the receptacle is within the reach of the pump’s power 
supply cord. DO NOT USE AN EXTENSION CORD.  Extension cords that 
are too long or too light do not deliver sufcient voltage to the pump motor. 
But more important, they could present a safety hazard if the insulation were 
to become damaged or the connection end were to fall into the sump.
3.  Testing for Ground. As a safety measure, each electrical outlet should be 
checked for ground using an Underwriters Laboratory Listed circuit analyzer 
which will indicate if the power, neutral and ground wires are correctly connected 
to your outlet. If they are not, call a qualied electrician.
4.  For Added Safety. Pump must be connected to a 3-prong grounded outlet 
interrupter device (ground fault circuit interrupter).
5.  FOR  YOUR  PROTECTION, ALWAYS  DISCONNECT  PUMP  FROM  ITS 
POWER SOURCE BEFORE HANDLING.  Single phase pumps are supplied 
with a 3-prong grounded plug to help protect you against the possibility of 
electrical shock.  DO NOT, UNDER ANY CIRCUMSTANCES, REMOVE THE 
GROUND PIN.  To reduce the risk of electrical shock, a properly grounded 
receptacle of grounding type  must be installed and protected by a ground 
fault circuit interrupter (GFCI) in accordance with national electrical code and 
local codes.
6.  Installation and checking of electrical circuits and hardware should only be 
performed by a qualied licensed electrician. 
7.  Risk of electric shock - These pumps have not been investigated for use in 
swimming pool areas.
8.  According to the state of California (Prop 65), this product contains chemicals 
known to the state of California to cause cancer and birth defects or other 
reproductive harm.
1.  Check to be sure your power source is  adequate for handling the voltage 
requirements of the motor, as indicated on the pump or basin plate. 
2.  Make sure the pump electrical supply circuit is equipped with fuses or circuit 
breakers of proper capacity. A separate branch circuit is recommended, sized 
according to the National Electrical Code for the current shown on the pump 
name plate. 
3.  All plumbing (discharge and vent lines) must be installed to meet local codes. 
Unit must be vented. DO NOT USE AN AUTOMATIC PLUMBING VENT 
DEVICE SIMILAR TO A "PRO-VENT". Some states require this product to 
be installed by a licensed plumber.
4.  Repair and service should be performed by Zoeller Pump Company Authorized 
Service Station only.
5.  CHECK VALVE MUST BE USED TO REDUCE UNNECESSARY CYCLING 
OF PUMP.  Check valve must be purchased separately on model 104 only. 
6.  Dewatering pumps are not designed or intended for handling raw sewage. 
7.  Maximum operating temperature for 105-131 Drain Pumps must not exceed 
130°F (54°C). 104 Drain Pumps are not to exceed 110°F (43°C).
8.  For health reasons, do not unplug, turn off, or disable pump and use pump 
tank system as a way to ll up a sink or laundry tray, etc.
9.  Unit is designed for above ground installation only.
SEE BELOW FOR LIST OF WARNINGS
CAUTION
SEE BELOW FOR LIST OF CAUTIONS
* MODEL 104 IS NOT
  IAPMO APPROVED.
U
P
C
®
C
COMPLIES WITH ASME A112.3.4
and CSA B45.9
REFER TO WARRANTY ON PAGE 2.
    Pumps with the “UL” mark and pumps with the “US” mark are tested to 
UL Standard UL778. CSA Certified pumps are certified to CSA Standard 
C22.2 No. 108.
Product information presented 
here reects conditions at time 
of  publication. Consult factory 
regarding discrepancies or 
inconsistencies.
MAIL TO:  P.O. BOX 16347 • Louisville, KY  40256-0347
SHIP TO:  3649 Cane Run Road  • Louisville, KY  40211-1961
(502) 778-2731 • 1 (800) 928-PUMP • FAX (502) 774-3624
visit our web site:
www.zoeller.com
®
Your Peace of Mind is Our Top Priority
®
Tuotetiedot
| Merkki: | Zoeller | 
| Kategoria: | Loisto | 
| Malli: | 131 | 
Tarvitsetko apua?
Jos tarvitset apua merkille Zoeller 131 esitä kysymys alla ja muut käyttäjät vastaavat sinulle
Loisto Zoeller Käyttöohjeet
                        
                         27 Maaliskuuta 2025
                        
                    
                                                            
                        
                         27 Maaliskuuta 2025
                        
                    
                                                            Loisto Käyttöohjeet
- Loisto Little Giant
- Loisto Blackburn
- Loisto Sicce
- Loisto Danfoss
- Loisto Nibe
- Loisto Bestway
- Loisto Aerotec
- Loisto Perlick
- Loisto Abac
- Loisto Grundfos
- Loisto Topeak
- Loisto SKS
- Loisto MSW
- Loisto T.I.P.
- Loisto Gardenline
Viimeisimmät Loisto Käyttöohjeet
                        
                         5 Huhtikuuta 2025
                        
                    
                                                            
                        
                         1 Huhtikuuta 2025
                        
                    
                                                            
                        
                         1 Huhtikuuta 2025
                        
                    
                                                            
                        
                         1 Huhtikuuta 2025
                        
                    
                                                            
                        
                         1 Huhtikuuta 2025
                        
                    
                                                            
                        
                         1 Huhtikuuta 2025
                        
                    
                                                            
                        
                         1 Huhtikuuta 2025
                        
                    
                                                            
                        
                         1 Huhtikuuta 2025
                        
                    
                                                            
                        
                         1 Huhtikuuta 2025
                        
                    
                                                            
                        
                         1 Huhtikuuta 2025