ADD ON OPTION FOR THE VP---6124/VP6124E
POWER SUPPLY
INTRODUCTION
The VP--6124UPS is an optional unit that allows the
VP---6124/VP6124E to supply power during a power
outage.
The VP----6124UPS is comprised of a VP6124UPS
(Charger) and a VBB-1424 (Battery Enclosure). The
VP---6124UPS connects to the VP6124 Power Supply
(To receive power to charge the batteries).
Listed below are specifications and recommendations
for power sources as well as precautionary
instructions.
UPS Float Standby Charging
Charging Voltage: 27.6 Volts (13.8 Volts per battery)
Current Limit: 900mA charging
100mA at 27 Volts final charge
Fusing: 1 Amp auto-reset polyswitch
6 Amps accidental reverse battery polyswitch
Time Required to Recharge Battery
7AH Battery: 14 hours
Length of Time Battery Will Provide
Power
•With four 7AH 12V batteries for 14AH total
3 Amps load draw:3 hours run time
6 Amps full load: 1.5 hours run time
Use of batteries greater than 7AH is not
recommended since 90% of all power outages are less
than an hour in length and the time to evacuate a
building is less than an hour.
NOTE: To insure trouble--free UPS backup
operation, five years batteries must be replaced five
years from the date of manufacturing.
DIMENSIONS/WEIGHT
•10.30"H x 3.50"W x 2.25"D
•(26.16cm H x 8.89cm W x 5.72cm D)
2.90 lbs. (1.32 kg)
INSTALLATION
The VP--6124UPS (Charger) is designed for wall
mounting only. Screw the mounting plate to the wall
near the VP---6124/VP6124E and position the
VP--6124UPS onto the mounting plate.
Attach the UPS unit securely to the bracket lip using
the 6--32 x 3/8" long Phillips head selftapping screw
supplied. Place the VBB-1424 on the floor within six
feet of the unit.
CONNECTIONS
•Disconnect AC power from the power supply.
•Remove plug button from the VP---6124/VP6124E.
•Remove wire access cover from the
VP---6124/VP6124E.
•Using the cable designated by the tag labeled
Valcom P/N WA-784 with four positions
connector and attached to VP--6124UPS
(Charger), place the Molex connector through the
hole on the power supply and connect the
charger to the Molex input connector on the
VP-6124 Power Supply.
•Snap strain relief into place.
•Replace wire access cover on the
VP---6124/VP6124E.
•Remove cover from Battery Backup.
•Push cable labeled Valcom P/N WA-783 with two
positions connector through the hole on the
battery enclosure and snap strain relief into
place.
Tuotetiedot
| Merkki: | Valcom |
| Kategoria: | Akkulaturi |
| Malli: | VP-6124-UPS |
Tarvitsetko apua?
Jos tarvitset apua merkille Valcom VP-6124-UPS esitä kysymys alla ja muut käyttäjät vastaavat sinulle
Akkulaturi Valcom Käyttöohjeet
15 Lokakuuta 2024
Akkulaturi Käyttöohjeet
Viimeisimmät Akkulaturi Käyttöohjeet
2 Huhtikuuta 2025
2 Huhtikuuta 2025
26 Maaliskuuta 2025
10 Maaliskuuta 2025
5 Maaliskuuta 2025
26 Helmikuuta 2025
20 Helmikuuta 2025
20 Helmikuuta 2025
15 Helmikuuta 2025
11 Helmikuuta 2025