Schneider LT4706 Käyttöohje
Sivut 4 Engels Ei luokiteltu
Lue käyttöohje merkille Schneider LT4706 ilmaiseksi verkossa tai lataa PDF. Ohje on ollut hyödyllinen 43 henkilölle. Kysyttävää mallista? Esitä kysymys

W9 1636671 01 A03
02 - 2011
1/4
www.schneider-electric.com
A
LT47
pp
0.5 - 6 A
Type
LT 4706
LT 4730
LT 4760
Relay setting range
3 - 30 A
5 - 60 A
Operating and Function
b LT47, solid state overload relay, compares motor
current with preset load current threshold (LOAD).
b Motor currents are monitored through two internal
current transformers.
b CT hole size is 12 mm in diameter. Please don't
allow excessive force on CTs.
b D-Time counts down and is only available for motor starting.
During steady state, if motor current is greater than current
setting(overloaded), LT47 switches its contacts after O-Time.
b For shear-pin (mechanical shock) protection, set O-Time knob
to its minimum in order to trip in 0.2-0.3 s.
DANGER
HAZARD OF ELECTRIC SHOCK,
EXPLOSION, OR ARC FLASH
Disconnect all power before servicing
equipment.
Failure to follow these instructions
will result in death or serious injury.
PLEASE NOTE:
b Electrical equipment should be installed, operated,
serviced, and maintained only by qualied personnel.
b No responsibility is assumed by Schneider Electric
for any consequences arising out of the use of this
material.
b This document is also available in French, Spanish,
Italian, German, and Chinese for download on our
website at www.schneider-electric.com.