Pentatech RA170Q Käyttöohje

Lue alta 📖 käyttöohje suomeksi merkille Pentatech RA170Q (2 sivua) kategoriassa Palovaroitin. Tämä opas oli hyödyllinen 34 henkilölle ja sai 4.8 tähden keskimäärin 17.5 käyttäjältä

Sivu 1/2
Where to locate
Installation
For minimum protection, smoke alarms should be installed in
every bedroom, children's room and hallway. In habitable
attics,asmokealarmshouldbeinstalledabovethestairs.
The alarm sound must be loud enough to wake sleeping
residentsinthecaseoffire.
In the case of open connections between floors, one smoke
alarmshouldbeinstalledoneachlevel.
Smoke alarms must be installedon theceiling, asclose to the
center of the ceiling as possible. The minimum distance to
walls,light fittings,electrical wiringsand applilances,beams,
andfurnituremustbe50cm.
the peak of the ceiling may prevent the smoke from rising.
Therefore in these rooms, thesmoke alarmsmust beinstalled
min.0.5mand max.1mfrom thepeakoftheceiling. Ceilings
withan inclination of 20°should be regardedas horizontal
ceilings.
InL-shapedrooms,thesmoke alarmshouldbeinstalledatthe
mitre line (see diagram). In large L-shaped rooms, each side
oftheroomshouldberegardedasaseparateroom.
Themaximuminstallation heightofa smokealarmshould not
exceed6m.
Rooms that are separated by partition walls, beams, or
theroom.
If the room is larger than 60m²,the installation of additional
smokealarmsisnecessary.
distance of a smoke alarm to the end wall must not exceed
7.5m. In each intersection, junction, and cornerof a hallway,
theremustbeonesmokealarm(mitreline).
The smoke alarm should be easily accessible to carry out
cleaningandtesting.
FurtherinformationaboutthelocationofsmokealarmscanbefoundintheDIN14676.
Ifabuildingistoocomplicatedortoolarge,pleasecontactasecurityexpertorthefiredepartment.
On thewall ornear doors,windows, openingsin theceiling, fansetc., where draftsmay blowaway smoke
orcausefalsealarms.
Inareaswherethetemperaturesareregularlybelow0°Corabove55°C.
Inhighhumidityareas(e.g.bathroom).
Insmallorpoorlyventilatedgaragesorkitchens,whereexhaustfumesorsteammaycausefalsealarms.
Ininsect-infectedareas.
Inplaceswhereyoucannoteasilyaccessthesmokealarmfortestingandcleaning.
In areas where air circulation may cause false alarms, e.g. in staircases outside the apartments (in
apartmenthouses).
Nearlightfittingsorelectricalwiringandappliances .
Nearextremelybrightlightsourcesordirectsunlight.
In areas where dust or dirt may impair the function of the smoke alarm or cause false alarms (e.g.
workshopsorbarns).
Inareaswhereheavycigarettesmokecanbeexpected.
Nearopenfireplaces,ovens,stovesetc.(minimumdistance4m).
<
Locationsto Avoid:
(minimumdistance50cm)
!
!
!
!
!
!
!
!
!
!
!
!
!
!
!
!
!
!
!
!
!
!
!
!
!
Userand InstallationManual
Properuse
Technicaldata
Package contents
Safety instructions
Please read this manual completely - it contains important information on the function, installation,
placement and maintenance of this product. Please keep this manual and hand it out to third persons, if
necessary. If this unit is installed by an installer, this manual must be handed out to the owner of the
apartmentafterinstallation.Ownersorresidentsareresponsibleformaintainingthesmokealarm.
Installationsite: Dateofinitialoperation:
Thissmokealarmdetectssmoke fromsmolderingfiresatanearlystageand warnswithaloudpulsatingalarm
(85 dBA/3 m). It is designedfor the use inprivate households and habitablerecreational vehicles and is not
approvedfor public,industrialor commercialbuildings. Thefields of operationof smoke alarmsare described
in DIN 14676. In the case of fire, smoke alarms can only give alarm, if the smoke reaches them. Everything
thatprevents thesmoke fromentering the smokealarm's housingmay delayor even preventthe alarm.A fire
inanotherroom,floor, orareaofthe homewillonlybe reportedwhenthesmoke reachesthesmokealarm. For
thisreason, youshould installa smokealarm in everyroom -at leastone oneach floor,observe theminimum
protection according to your locallegislation. Smokealarms areno substitute for a property or life insurance.
Appropriatecoverageisyourresponsibility.Thissmokealarmisnotsuitablefordeafpersons.
Contaminationof the smokealarm bydust ordirt may leadto falsealarms. Ifthe dirtcannotbe removedfrom
outsideasdescribedin thechapter"Maintenance/Cleaning",the unithastobereplaced byanewone.There is
nowarranty fordirty units.This smokealarm is equippedwith abuilt-in non-exchangeablebattery andhas to
bereplacedafter 10yearsof operationatthe latest. A reliableearlywarning offireand smokeisonly given,if
thissmokealarmisusedaccordingtotheseinstructions.
Unlessthereisastatutoryobligation,themanufacturerisnotresponsibleforfurtherclaims,including personal
ormaterialdamages,arisingfromtheuseoftheproductorfromnonfunctionormalfunctionoftheproduct.
Operatingvoltage: 3V DC
Powersupply: 1pc.3Vbuilt-inlithium battery
Batterylifetime: 10years*
Batterywarning: upto30days,onebeepapprox.every40seconds
Smokesensor: photoelectric
Warningsound: piezo-electric,85dB(A)at3m
Operationindication: statusindicatorflashesweaklyapprox.every40seconds
Alarmsilencingindication: statusindicatorflashesweaklyapprox.every5seconds
Testbutton: totestelectronics,batteryandwarningsound
Temperaturerange: to+55°C
Airhumidity: 20%to 80%
Tests: according to DIN EN 14604 and vfdb 14-01, produced in
certifiedproductionsiteaccordingtoISO9001
*calculatedlifeexpectancyinnormaluse,at21°C,withoutalarmtriggering
Smoke alarm with built-in battery and mounting plate
3M adhesive pad
Do not damage any gas, electricity, water or telecommunication lines during drilling and fixing work.
Otherwisetherearedangersoffire,personalandfatal injury.
Ensure thatthe alarm sirenis not activated next to somebody's ear. Otherwise there is a dangerof hearing
damage!
Donotpaintorpaste thesmokealarm,anddonotcoverit, otherwiseitsfunctionwillbeimpaired.
Avoid touching leaking or damagedbatteries! Use suitable safety glovesand clothing! Otherwise you may
riskinjurybycausticacid!
Donotshort-outbatteries,anddonotrechargethem.Otherwiseyoumayriskdeathbyexplosion!
Donottytoopenthem,anddonotburnthem!Otherwisethereisdangerofexplosion!
"
!
!
!
!
!
!
!
!
RA170Q
SMOKE ALARM
WITH 10 YEAR LONG LIFE BATTERY
Indexa GmbH
Paul-Böhringer-Str. 3
D-74229 Oedheim
Germany
Subject to change, 2024/03/18
Extended test according
to vfdb 14-01
24
1116
Declaration of Performance: RA170Q-DoP-001
1116-CPR-181-3
EN 14604:2005+AC:2008
Purpose: fire protection (smoke detector)
SMOKE ALARM RA170Q
Declaration of Performance according to CPR
available at www.indexa.de
1.
2.
Mounting plate
Holes for screws
3. Brackets
4. Openings
5. Button
6. Status indicator
1 2 3 3 2 4 4 5 6
!
!
2 x screws and 2 x plugs
User and installation manual
Example: large hallway
Example: L-shaped room
Example: apartment
Example: multi-storey home
smoke alarm: minimum protection
smoke alarm: increased protection
bedroom
bathroom
kitchen
bedroom
bedroom
living
room
attic
bedroom bedroom
living room
dining room
basement
basement
1/2
1/2
1/2
1/2
max. 15 m
max. 7.5 m

Tuotetiedot

Merkki: Pentatech
Kategoria: Palovaroitin
Malli: RA170Q

Tarvitsetko apua?

Jos tarvitset apua merkille Pentatech RA170Q esitä kysymys alla ja muut käyttäjät vastaavat sinulle