Entes MPR-53S-DIN Käyttöohje
                    Entes
                    
                    Ei luokiteltu
                    
                    MPR-53S-DIN
                
                                
                
                
                                
                Lue alta 📖 käyttöohje suomeksi merkille Entes MPR-53S-DIN (20 sivua) kategoriassa Ei luokiteltu. Tämä opas oli hyödyllinen 34 henkilölle ja sai 4.7 tähden keskimäärin 17.5 käyttäjältä
                        Sivu 1/20
                    
                    
                    
NETZANALYSATOR
MPR-53S
MODBUS REGISTERTABEL
NETWORK ANALYZER
MPR-53/53S
20 1
MODBUS REGISTERTABEL
 ADRESSE  ADRESSE  REGISTER  R/W  BEREICH  EINHEIT  MULTIPLIKATOR  FORMAT
  (HEX)
  152  0098    L3 PHASE MIN. SCHEINLEISTUNG  R/W  (0 - 18000)xCTxVT  VA  0.1  unsigned int
  154  009A  GESAMTE MIN. IMPORTIERTE WIRKLEISTUNG  R/W  (-18000 - 18000)xCTxVT  Watt  0.1  int
  156  009C  GESAMTE MIN. EXPORTIERTE WIRKLEISTUNG  R/W  (-18000 - 18000)xCTxVT  Watt  0.1  int
  158  009E  GESAMTE MIN. INDUKTIVE BLINDLEISTUNG  R/W  (-18000 - 18000)xCTxVT  Var  0.1  int
  160  00A0  GESAMTE MIN. KAPAZITIVE BLINDLEISTUNG  R/W  (-18000 - 18000)xCTxVT  Var  0.1  int
  162  00A2  GESAMTE MIN. SCHEINLEISTUNG  R/W  (0 - 18000)xCTxVT  VA  0.1  unsigned int
  164  00A4  L1 PHASE MAX. SPANNUNG  R/W  (0 - 3000)xUT  Volt  0.1  unsigned int
  166  00A6  L2 PHASE MAX. SPANNUNG  R/W  (0 - 3000)xUT  Volt  0.1  unsigned int
  168  00A8  L3 PHASE MAX. SPANNUNG  R/W  (0 - 3000)xUT  Volt  0.1  unsigned int
  170  00AA  L1-L2 PHASE-PHASE MAX. SPANNUNG  R/W  (0 - 5000)xUT  Volt  0.1  unsigned int
  172  00AC  L2-L3 PHASE-PHASE MAX. SPANNUNG  R/W  (0 - 5000)xUT  Volt  0.1  unsigned int
  174  00AE  L3-L1 PHASE-PHASE MAX. SPANNUNG  R/W  (0 - 5000)xUT  Volt  0.1  unsigned int
  176  00B0  L1 PHASE MAX. STROM  R/W  (0 - 6000)xCT  Amper  0.001  unsigned int
  178  00B2    L2 PHASE MAX. STROM  R/W  (0 - 6000)xCT  Amper  0.001  unsigned int
  180  00B4  L3 PHASE MAX. STROM  R/W  (0 - 6000)xCT  Amper  0.001  unsigned int
  182  00B6    L1 PHASE MAX. WIRKLEISTUNG  R/W  (-18000 - 18000)xCTxVT  Watt  0.1  int
  184  00B8  L2 PHASE MAX. WIRKLEISTUNG  R/W  (-18000 - 18000)xCTxVT  Watt  0.1  int
  186  00BA    L3 PHASE MAX. WIRKLEISTUNG  R/W  (-18000 - 18000)xCTxVT  Watt  0.1  int
  188  00BC  L1 PHASE MAX. BLINDLEISTUNG  R/W  (-18000 - 18000)xCTxVT  Var  0.1  int
  190  00BE    L2 PHASE MAX. BLINDLEISTUNG  R/W  (-18000 - 18000)xCTxVT  Var  0.1  int
  192  00C0  L3 PHASE MAX. BLINDLEISTUNG  R/W  (-18000 - 18000)xCTxVT  Var  0.1  int
  194  00C2    L1 PHASE MAX. SCHEINLEISTUNG  R/W  (0 - 18000)xCTxVT  VA  0.1  unsigned int
  196  00C4  L2 PHASE MAX. SCHEINLEISTUNG  R/W  (0 - 18000)xCTxVT  VA  0.1  unsigned int
  198  00C6    L3 PHASE MAX. SCHEINLEISTUNG  R/W  (0 - 18000)xCTxVT  VA  0.1  unsigned int
  200  00C8  GESAMTE MAX. IMPORTIERTE WIRKLEISTUNG  R/W  (-18000 - 18000)xCTxVT  Watt  0.1  int
  202  00CA  GESAMTE MAX. EXPORTIERTE WIRKLEISTUNG  R/W  (-18000 - 18000)xCTxVT  Watt  0.1  int
  204  00CC  GESAMTE MAX. INDUKTIVE BLINDLEISTUNG  R/W  (-18000 - 18000)xCTxVT  Var  0.1  int
  206  00CE  GESAMTE MAX. KAPAZITIVE BLINDLEISTUNG  R/W  (-18000 - 18000)xCTxVT  Var  0.1  int
  208  00D0  GESAMTE MAX. SCHEINLEISTUNG  R/W  (0 - 18000)xCTxVT  VA  0.1  unsigned int
  210  00D2    L1 PHASE MAX. STROMBEDARF  R/W  (0 - 6000)xCT  Amper  0.001  unsigned int
  212  00D4  L2 PHASE MAX. STROMBEDARF  R/W  (0 - 6000)xCT  Amper  0.001  unsigned int
  214  00D6    L3 PHASE MAX. STROMBEDARF  R/W  (0 - 6000)xCT  Amper  0.001  unsigned int
  216  00D8 
L1 PHASE IMPORTIERTE MAX.  BEDARF WIRKLEISTUNG
  R/W  (-18000 - 18000)xCTxVT  Watt  0.1  int
  218  00DA 
L1 PHASE EXPORTIERTE MAX.  BEDARF WIRKLEISTUNG
  R/W  (-18000 - 18000)xCTxVT  Watt  0.1  int
  220  00DC 
L2 PHASE IMPORTIERTE MAX.  BEDARF WIRKLEISTUNG
  R/W  (-18000 - 18000)xCTxVT  Watt  0.1  int
  222  00DE   
L2 PHASE EXPORTIERTE MAX.  BEDARF WIRKLEISTUNG
  R/W  (-18000 - 18000)xCTxVT  Watt  0.1  int
  224  00E0 
L3 PHASE IMPORTIERTE MAX.  BEDARF WIRKLEISTUNG
  R/W  (-18000 - 18000)xCTxVT  Watt  0.1  int
  226  00E2  L3 
PHASE EXPORTIERTE MAX.  BEDARF WIRKLEISTUNG
  R/W  (-18000 - 18000)xCTxVT  Watt  0.1  int
  228  00E4 
L1 PHASE INDUKTIVE MAX. BEDARF BLINDLEISTUNG
  R/W  (-18000 - 18000)xCTxVT  Var  0.1  int
  230  00E6 
L1 PHASE KAPAZITIVE MAX. BEDARF BLINDLEISTUNG
  R/W  (-18000 - 18000)xCTxVT  Var  0.1  int
  232  00E8 
L2 PHASE INDUKTIVE MAX. BEDARF BLINDLEISTUNG
  R/W  (-18000 - 18000)xCTxVT  Var  0.1  int
  234  00EA 
L2 PHASE KAPAZITIVE MAX.  BEDARF  BLINDLEISTUNG
  R/W  (-18000 - 18000)xCTxVT  Var  0.1  int
  236  00EC 
L3 PHASE INDUKTIVE MAX. BEDARF BLINDLEISTUNG
  R/W  (-18000 - 18000)xCTxVT  Var  0.1  int
  238  00EE 
L3 PHASE KAPAZITIVE MAX.  BEDARF  BLINDLEISTUNG
  R/W  (-18000 - 18000)xCTxVT  Var  0.1  int
  240  00F0  L1 PHASE MAX. BEDARF SCHEINLEISTUNG  R/W  (0 - 18000)xCTxVT  VA  0.1  unsigned int
  242  00F2    L2 PHASE MAX. BEDARF SCHEINLEISTUNG  R/W  (0 - 18000)xCTxVT  VA  0.1  unsigned int
  244  00F4  L3 PHASE MAX. BEDARF SCHEINLEISTUNG  R/W  (0 - 18000)xCTxVT  VA  0.1  unsigned int
  246  00F6 
GESAMTE IMPORTIERTE MAX. BEDARF WIRKLEISTUNG
  R/W  (-18000 - 18000)xCTxVT  Watt  0.1  int
  248  00F8 
GESAMTE EXPORTIERTE MAX. BEDARF WIRKLEISTUNG
  R/W  (-18000 - 18000)xCTxVT  Watt  0.1  int
  250  00FA  GESAMTE INDUKTIVE MAX. BEDARF BLINDLEISTUNG  R/W  (-18000 - 18000)xCTxVT  Var  0.1  int
  252  00FC  GESAMTE KAPAZITIVE MAX. BEDARF BLINDLEISTUNG  R/W  (-18000 - 18000)xCTxVT  Var  0.1  int
  254  00FE  GESAMTE MAX. BEDARF SCHEINLEISTUNG  R/W  (0 - 18000)xCTxVT  VA  0.1  unsigned int
ADRESSE  ADRESSE  REGISTER  R/W  BEREICH  EINHEIT  MULTIPLIKATOR  FORMAT
  (HEX)
  32768  8000  SPANNUNGWANDLERVERHÄLTINS  R/W  0-40000  -  0.1  short- int
  32769  8001  STROMVANDLERVERHÄLTNIS  R/W  0-2000  -  1  short- int
  32770  8002  BERECHUNGSMETHODE  R/W  0-5  -  -  short- int
  32771  8003  BEDARFSZEIT  R/W  1-60  minuten  1  short- int
  32772  8004  IMPULSRATE  R/W  0-6  -  -  short- int
  32773  8005  IMPULSAUSGANG 1 PARAMETEREINSTELLUNG  R/W  0-5  -  -  short- int
  32774  8006  IMPULSAUSGANG 2 PARAMETEREINSTELLUNG  R/W  0-5  -  -  short- int
  32775  8007  ENERGIEZAHLER 1 AUSWAHL   R/W  0-3  -  -  short- int
  32776  8008  ENERGIEZAHLER 2 AUSWAHL   R/W  0-3  -  -  short- int
  32777  8009  KOMMUNIKATIONSADRESSE  R/W  0-247  -  -  short- int
  32778  800A  BAUDRATE  R/W  1-5  -  -  short- int
  32779  800B  PARITÄT  R/W  0-2  -  -  short- int
  32780  800C  KENNWORTAKTIVIERUNG  R/W  0-1  -  -  short- int
  32781  800D  KENNWORT  R/W  0-9999  -  -  short- int
 IMPULSEAUSGANG 1-2  IMPULSERATE 0-6:  ENERGIEZÄHLER 1 AUSWAHL 0-3:  1-5-BAUDRATE
PARAMETEREINSTELLUNG 0-5  0:1 Watt / Impulse  0: Ein (EC will für alle Konditionen zählen)  1: 38400 bps
0: Aktiv  1:10 Watt / Impulse  1: EC1 will zählen nur wenn Digitaleingang 1(activ) ist  2: 19200 bps
1: Importierte Aktiv  2:100 Watt / Impulse  2: EC1 will zählen nur wenn Digitaleingang 2(activ) ist  3: 9600 bps
2: Exportierte Aktiv  3:1 kW / Impulse  3: EC1 will zählen nur wenn EC2 nicht zählt  4: 4800 bps
3: Reaktiv  4:10 kW / Impulse       5: 2400 bps
4: Importierte Reaktiv  5:100 kW / Impulse  ENERGIEZÄHLER 2 AUSWAHL 0-3: 
5: Exportierte Reaktiv  6: 1 MW / Impulse  0: Ein (EC will für alle Konditionen zählen)  0-2-PARITÄT :
    1: EC will zählen nur wenn Digitaleingang1 1(activ) ist  0: Keine
BERECHUNHD 0-5 :    2: EC will zählen nur wenn Digitaleingang2 1(activ) ist  1: Ungerade
Bitte sehen Sie “Einstellung der    3: EC2 will zählen nur wenn EC1 nicht zählt  2: Gerade
Blindenergieberechungsmethode” auf zweite Seite 
    0-1 KENNWORTAKTIVIERUNG : 
    0: Inactiv 
    1: Aktiv 
General
MPR-53/53S is developed for measuring all the electrical parameters on the 
network. Measured parameters are shown in 5 separate displays.This allows to 
monitor more than 50 parameters at the same time. MPR-53S has also MODBUS 
serial interface feature.
Using of MPR-53/53S:
Parameters are shown in L1, L2, L3 displays (VLN; VLL; A; IN; W; VAr; VA; Cos 
; kWh, kVarh, THD) by using up-down buttons. Total Active (SW), Total Apparent 
Power (SVA) and Frequency (Hz) are selected by back button.
Total Reactive Power (SVAr) and Cos   are selected by Esc button.
Digital Inputs
MPR-53/53S has 2 digital inputs which are used to monitor the status of electrical 
contacts. Digital input has 2 functions : 
- Enabling remote control of the data received through the digital input terminal   
(battery, thermostat, circuit breaker, pumps status)
- Controlling energy counters when digital inputs are activated at Energy count 
menu. (Example: It is used for measuring of energy separately at the using of 
network and generator).
Energy Pulse Outputs
MPR-53/53S  has 2 Energy Pulse Outputs. These outputs give the pulses only for 
E-1 (Energy Counter). Pulse outputs can be congurable separately. 
Pul1 and Pul2: In “o-1 (Pulse1)”, “o-2 (Pulse2)” menus which are in the pulse menu, 
device give pulse according to selected energy parameters as [Active energy (ACt, 
A-I, A-E), Reactive energy (rEA, r-L, r-C)].
Please refer to the pulse menu for the coefcients of energies. 
Monitoring of Min.,Max. and Max. Demand Values:
Min. and max. values are dened for VLN, VLL, A, W, VAr, VA, SW, SVAr, SVA; 
demand values are dened for A, W, VAr, VA, SW, SVA, SVAr.
If measured instant value is smaller than min. value which was stored before, it is 
stored as new min. value. If measured instant value is greater than max. value which 
was stored before, it is stored as new max. value. 
Demand value is the average value of the measured values in demand time (15 
minute). 
If one of dened parameters is displayed (ie. “A”) when deman button is pressed 
min., max or max. demand values are displayed. When an undened parameter 
is displayed (ie. “Cos ”) if demand button is pressed, instant value is continued to 
display.      
Monitoring THD Values
When “V
LN
” and “THD” leds light on, voltage THD is monitored and also if “A” and 
“THD” leds light on, current THD is monitored.
Monitoring Neutral Current
Neutral current can be monitored by scrolling after 3-phases current values has 
displayed.
H-L-M LEDs
H-L-M LEDs are dedicated to displaying the min., max. and max. demand values 
according to selected parameters.
H: Maximum Value, L: Minimum Value, M: Max. Demand Value 
Calculation Methods for Active / Reactive Power Values
If the led on the most left side blinks it represents that active power’s / reactive 
power’s direction is negative.
There are two methods for calculating total active and total reactive powers:
1) Active / Reactive power can be calculated by summing import and export values 
and displaying as a single value.
2) Active / Reactive power can be calculated according to direction as
import / export.
Note :
1) The dot at the most right digit of the fourth display (During SW is displayed) 
represents that displayed value is export active power value. Vice versa, 
displayed value is import active power value.
2) The dot at the most right digit of the fourth display (During SVAr is 
displayed) represents that displayed value is capacitive reactive power value. 
Vice versa, displayed value is inductive reactive power value. 
3) The displayed parameter will not change if power is off after 30 seconds of 
stand-by (ie. A).
Measured Parameters:
V   (Phase Voltage )  CosLN
  THD (Total Harmonic    
    Distortion)
V (Phase to Phase Voltage)  AI ( kWh) (Import Active Energy I)  Hz. (Frequency)LL 
A (Phase Current, Neutral Current)  AE (kWh) (Export Active Energy)  SW (Total Active Power)
W (Active Power)  rI (kVArh) (Import Reactive Energy)  SVAr (Total Reactive Power)
VAr (Reactive Power)  rE(kVArh) (Export Reactive Energy)   SVA (Total Apparent Power)
VA (Apparent Power)          
FUNCTIONS OF BUTTONS
In the monitoring mode, it is used to switch between(V
LN
, V
LL
, A, W, VAr, VA, 
Cos , kWh, kVarh, THD) parameters. 
At the programming mode, it provides to increase value of desired 
parameter and pass to the next menu.
In the monitoring mode, it is used to pass between(V
LN
, V
LL
, A, W, VAr, VA, 
Cos , kWh, kVarh, THD) parameters. 
At the programming mode, it provides to decrease value of desired 
parameter and pass to the prevides menu. 
(SET) In the monitoring mode, it is used to switch between min., max., 
demand and instant values. When it is pressed for 3 seconds, programming 
mode it is entered.
In the programming mode, it is used for saving parameters and moving to 
the sub menu.
(Back) In the monitoring mode, it is used to switch between SW, SVA and 
Hz parameters. It used to switch to the previous digit in submenu. 
(ESC) In the monitoring mode, it provides to switch between SVAr and Cosj 
values. In the programming mode, it is used to enter to the upper menu or  
it is used to quit from the programming mode without saving values.
If user password is activated and set button is pressed for 3 seconds, 
a pin code is required in order to enter to the menu.
Current Transformer Ratio Setup
In this menu, current transformer ratio is set between 1 - 2000.
Note: If the current transformer is not used between the system and 
MPR-53/53S, current transformer ratio is entered as ‘1’. 
Example: If a current transformer which has a ratio of 250/5A is used 
between the system and MPR-53/53S; Current transformer ratio is 
entered as “50” (250/5).
Press SET button for 3 seconds (trA Fo menu is displayed)
Press SET button; trA Fo Ctr menu is displayed (In CT-25 adapted 
devices, trA Fo trn is displayed instead.)
( : trA Fo Utr menu can be displayed by scrolling the UP/DOWN Not
buttons.)
Press SET button. Blinking the rst digit of displayed value appears.
(trA Fo Utr menu can be programmed similarly.)
Enter the blinking digit value by scrolling UP/DOWN buttons. Switch 
to the other digits by using SET button, use BACK button to go to 
previous digit. After you entered the last digit press SET button, “trA 
Fo Ctr / trA Fo trn / trA Fo Utr” is displayed. “on” can be selected by 
scrolling UP/DOWN buttons. (Data is entered but is not activated 
yet. For activating the new data please follow the below steps).
Press ESC button one by one until “SAU E  SEt  yES” is displayed.
Press SET button. When “SAU E  SEt  yES” is displayed, if you press 
ESC button or choose “no” option instead of “yES” option by using 
UP-DOWN buttons, new data will be cancelled and previous value will 
be activated.
Tuotetiedot
| Merkki: | Entes | 
| Kategoria: | Ei luokiteltu | 
| Malli: | MPR-53S-DIN | 
Tarvitsetko apua?
Jos tarvitset apua merkille Entes MPR-53S-DIN esitä kysymys alla ja muut käyttäjät vastaavat sinulle
Ei luokiteltu Entes Käyttöohjeet
                        
                         13 Helmikuuta 2025
                        
                    
                                                            
                        
                         2 Tammikuuta 2025
                        
                    
                                                            
                        
                         2 Tammikuuta 2025
                        
                    
                                                            
                        
                         26 Joulukuuta 2024
                        
                    
                                                            
                        
                         16 Lokakuuta 2024
                        
                    
                                                            
                        
                         16 Lokakuuta 2024
                        
                    
                                                            
                        
                         16 Lokakuuta 2024
                        
                    
                                                            
                        
                         16 Lokakuuta 2024
                        
                    
                                                            
                        
                         16 Lokakuuta 2024
                        
                    
                                                            
                        
                         16 Lokakuuta 2024
                        
                    
                                                            Ei luokiteltu Käyttöohjeet
- Ei luokiteltu Manfrotto
- Ei luokiteltu Miniland
- Ei luokiteltu Triton
- Ei luokiteltu Hobby
- Ei luokiteltu Powerplus
- Ei luokiteltu Sportime
- Ei luokiteltu DBX
- Ei luokiteltu Spanninga
- Ei luokiteltu Medela
- Ei luokiteltu Kendall Howard
- Ei luokiteltu JoeCo
- Ei luokiteltu IsoTek
- Ei luokiteltu Alutruss
- Ei luokiteltu Trezor
- Ei luokiteltu Bravilor Bonamat
Viimeisimmät Ei luokiteltu Käyttöohjeet
                        
                         9 Huhtikuuta 2025
                        
                    
                                                            
                        
                         9 Huhtikuuta 2025
                        
                    
                                                            
                        
                         9 Huhtikuuta 2025
                        
                    
                                                            
                        
                         9 Huhtikuuta 2025
                        
                    
                                                            
                        
                         9 Huhtikuuta 2025
                        
                    
                                                            
                        
                         9 Huhtikuuta 2025
                        
                    
                                                            
                        
                         9 Huhtikuuta 2025
                        
                    
                                                            
                        
                         9 Huhtikuuta 2025
                        
                    
                                                            
                        
                         9 Huhtikuuta 2025
                        
                    
                                                            
                        
                         9 Huhtikuuta 2025