Description
Operation
The ATS-10providesthemainsvoltagemonitoringandautomatictransferswitching.Intheeventofamains
voltagefailure,theremotestartrelayoutputisenergizedandtheunitautomaticallytransferstheloadfromthe
mainstothegenerator.Microprocessortechnologyallowsexactmeasurement,setpointadjustmentandtiming
functionswiththeparameterstobesimplyprogrammedanddisplayedfromthefrontpanel.
The ATS-10automatictransferswitchcandetectfailureofanyphaseofthemainssupply.Ifatleastoneofthe
mainsphasevoltagesgoesoutsidesetlimits,theunitoperatesasfollows:
- The ledturnsfromgreentored. Themainscontactoroutputisdeenergizedandthe
green ledisextinguished.
- TheremotestartoutputisenergisedaftertheRemoteStartDelayparameterhasexpired. Thegenerator
startmodulereceivesthissignalandinitiatestheenginestart.
-IftheUnitUsage Typeparameter(P00)isselectedas0(Type-1);Whenthegeneratorvoltageiswithinset
limits,theyellow ledwillilluminate. Theunitwillallowthegeneratingsettorunwithout
loaduntiltheEngineHeatingPeriodparameterisexpired. Afterthistime,theyellow
ledwillstartblinkingandtheunitwaitfortheGeneratorContactorDelayparameter.
IftheUnitUsage Typeparameter(P00)isselectedas1(Type-2);WhentheEnginerunningsignalis
present,theyellow ledwillilluminate. Theunitwillallowthegeneratingsettorun
withoutloaduntiltheLoadgen.signalispresent.Ifthissignalispresent,theyellow
ledwillstartblinkingandtheunitwaitfortheGeneratorContactorDelayparameter.
- Thegeneratorcontactoroutputwillbeenergizedandtheyellow ledwill
illuminatesteadilywhentheGeneratorContactorDelayparameterisexpired.
-Ifthemainsvoltagereturntowithinlimits,the ledwillturntogreenandtheunitwaits
fortheMainsReturndelayparameterforthemainsvoltagestabilization.
-WhentheMainsReturnDelayparameterisexpired,theyellow ledis
extinguishedandthegeneratorcontactoroutputisdeenergized. Thenthegreen
ledwillstartblinkingandthentheunitwillwaitfortheMainscontactorDelayparameter.
-WhentheMainscontactorDelayparameterisexpired,thegreen ledwill
illuminatesteadilyandthemainscontactoroutputisenergized. Thentheremotestartoutputisdeenergized.
- Theunitisreadyforanewmainsfailure.
The ATS-10hasgota TEST modefeature. Thismodeallowsthegeneratingsettobetestedwithouttakingthe
load. ThismodeisalsocalledEmergencybackupmodewhichkeepsthegeneratingsetrunningandmakesa
quicktransferifamainsfailureoccurs.
Inthismode, Theremotestartoutputwillbeenergizedbutnoloadtransferwilltakeplaceunlesstheoccurrenceof
amainsfailure.Ifamainsfailureoccurs,theloadwillbetransferredtothegeneratingset.Ifthemainsvoltage
returntowithinlimitsandtheMainsReturnDelayparameterisexpired,theloadwillbetransferredtothemains,
butthegeneratingsetwillbekeptrunning. Theremotestartoutputwillonlydeenergizedwhenthe Testmodeis
cancelled.
MainsVoltageOkay
MainsContactorClosed
GeneratorRunning
GeneratorContactor
Closed
GeneratorRunning
GeneratorContactor
Closed
GeneratorContactorClosed
MainsVoltageOkay
GeneratorContactorClosed
MainsContactorClosed
MainsContactorClosed
1
Automatic Transfer Switch, 72x72 DIN Size
ATS-10
Automatic Transfer Switch
72 x 72 DIN Size
IntroductionBrochure.ENG ATS-1001V0207/16