990-0374A revision 2 11/01
This adendum does not apply to Bak-UPS Po 1000/1400 and Smart-UPSV/S 1000/1400dcr
I.Installation
Follow the installation illustration on the accompanying sheet.
Note: Small sparks at the battery connectors are normal during connection.
II.Post-Installation
Once installed,
allow the unit to charge for five hours. If the unit is an XL model, allow it to charge for
24 hours.
Note:The Smart-UPS will charge whether it is on or off, and will charge whether there is a load
present or not. In situations where the power quality is poor, it is recommended that the unit be
shutdown during this charging period. A Smart-UPS that is powered on may switch to battery
operation which would prolong the time needed to fully recharge the battery.
III. Clearing the Replace Battery LED
A.In order for the replace battery LEDvalidto be cleared, it is necessary to run a self test. For a self test
to be considered valid, the following conditions must be satisfied:
■battery capacity must be greater than 75%(minimum of four battery bar graph LEDs illuminated)
or
■Smart-UPS must have been charging for at least 8 hours from the last low battery condition. (Low
battery condition refers to a state when the Smart-UPS battery has fully discharged).
B.Ways to initiate a self test
A self test can be initiated in any one of five ways:
■Start up of the UPS
■Smart-UPS front panel test button
■Powerchute PLUS software
■SmartSlot Accessory
■Automatic timer- every two weeks from turn on (see APC owners manuals for details)
IV. Verifying Operation
A.What happens during a self test?
When a self test is initiated, the unit supports the load while operating on battery for approximately
8-10 seconds. During this period, the Smart-UPS determines the health of the battery.
B.When should the self test be performed?
After the unit has charged for five hours, a self test can be performed.
Replacement Battery Cartridge(RBC) Addendum
RBC5, RBC6, RBC7, RBC8, RBC9, RBC11, RBC12, RBC22, RBC23, RBC24, RBC25,
RBC27, RBC28, RBC5I, RBC6I, RBC7I, RBC8I, RBC9I, RBC11I, RBC12I, RBC22I,
RBC23I, RBC24I, RBC25I, RBC5J, RBC6J, RBC7J, RBC8J, RBC11J, RBC12J,
Tuotetiedot
| Merkki: | Apc |
| Kategoria: | UPS |
| Malli: | RBC9 |
Tarvitsetko apua?
Jos tarvitset apua merkille Apc RBC9 esitä kysymys alla ja muut käyttäjät vastaavat sinulle
UPS Apc Käyttöohjeet
Apc Back-UPS BX650CI-GR Käyttöohje Apc Back-UPS BX950U-FR Käyttöohje Apc Back-UPS BX650LI Käyttöohje Apc Easy UPS BVX1000UXI Käyttöohje Apc RBC22 Käyttöohje Apc AP9626 Käyttöohje Apc 66077 Käyttöohje Apc 66057 Käyttöohje
Suosittuja kategoriassa UPS
UPS Käyttöohjeet
Viimeisimmät UPS Käyttöohjeet
CyberPower SM120KMF Käyttöohje CyberPower UT2200EI Käyttöohje CyberPower UT1000E Käyttöohje CyberPower Value2200ELCD Käyttöohje Block PC-1024-050-0 Käyttöohje Block PVUA 24/24-10 Käyttöohje Tripp Lite S3MT-60KWR480V Käyttöohje CyberPower BR700ELCD Käyttöohje CyberPower CPS600E Käyttöohje CyberPower PR5000ELCDRTXL5U Käyttöohje